Number of poles 3P
Rated operating voltage [Ue] Power circuit: <= 1000 V AC 25...400 Hz. .400 Hz
Power supply circuit: <= 460 V DC
Rated operating current [Ie] 1000 A (at operating temperature <= 40 °C) at operating voltage <= <= 440 V AC AC-1 for power circuits
620 A (at operating temperature <= 40 °C) at operating voltage <= <= 440 V AC AC-3 for power supply circuits
[Uc] control circuit voltage 220 V AC 50/60 Hz
Loop contact type 3 NO
Protective cover None
Approximate heating current [Ith] 1000 A (at operating temperature <=40 °C) for power supply circuits
Rated short-time withstand current [Icw] 5050 A at operating temperatures <= 40 °C for 10 s for power supply circuits
4400 A at operating temperatures <= 40 °C for 30 s for power circuits
3400 A at operating temperatures <= 40 °C for 1 minute for power circuits
2200 A at operating temperatures <= 40 °C for 3 minutes for power circuits
1600 A for 10 minutes at operating temperatures <= 40 °C for power circuits
800 A gG at operating voltage <= <= 440 V, for power circuits
630 A aM at operating voltages <= <= 440 V, for power circuits
1000 A gG at operating voltages <= <= 440 V for power circuits
Average impedance 0.12 mΩ - Ith 1000 A 50 Hz for power circuits
Rated insulation voltage [Ui] power circuit: 1000 V according to IEC 60947-4-1
Overvoltage category III