Menu
Your Cart

Ultrasonic Sensor UM30-211113,part no. 6036916,30-250MM,SYMBOL: 0-991473,ANALOGUE OUTPUT:0-10V/10-20mA

Ultrasonic Sensor UM30-211113,part no. 6036916,30-250MM,SYMBOL: 0-991473,ANALOGUE OUTPUT:0-10V/10-20mA
Ultrasonic Sensor UM30-211113,part no. 6036916,30-250MM,SYMBOL: 0-991473,ANALOGUE OUTPUT:0-10V/10-20mA
  • MODEL: UM30-211113
  • LEAD TIME: in stock
$244.16

Product data sheet

Mechanics/electronics

Supply voltage Vs DC 9 V ... 30 V 1) 2)

Power consumption ≤ 2.4 W 3)

Initialization time < 300 ms

Design Cylindrical

Housing material Metal (nickel-plated brass, PBT, ultrasonic transducer: polyurethane foam, glass epoxy resin)

Thread size M30 x 1.5

Connection type Male connector, M12, 5-pin

Indication LED display, 2 x LED

Weight 150 g

Sending axis Straight

Dimensions (W x H x D) 30 mm x 30 mm x 84 mm

Enclosure rating IP65 / IP67

Protection class III

1) Limit values, reverse-polarity protected Operation in short-circuit protected network: max. 8 A, class 2.

2) 15 V ... 30 V when using the analog voltage output.

3) Without load.

Safety-related parameters

MTTFD 101 years 

DCavg 0%

Performance

Operating range, limiting range 30 mm ... 250 mm, 350 mm

Target Natural objects

1) In relation to the current measured value, minimum value ≥ resolution.

2) Referring to current measurement value.

3) Temperature compensation can be switched off, without temperature compensation: 0.17 % / K.

4) Subsequent smoothing of the analog output, depending on the application, may increase the response time by up to 200 %. 

Resolution ≥ 0.18 mm

Repeatability ± 0.15 %

Accuracy ± 1 % 

Temperature compensation ✔

Response time 32 ms 4) Output time 8 ms

Ultrasonic frequency (typical) 320 kHz

Detection area (typical) See diagrams

Additional function Teach-in of analog output Scaling of analog outputs Invertable analog output Synchronization of up to 50 sensors Multiplexing: no cross talk of up to 50 sensors Adjustable measurement filters: Measured value filters/Filter strength/Foreground suppression/Detection area/Sensitivity and sound beam Display (can be deactivated) Reset to factory default

1) In relation to the current measured value, minimum value ≥ resolution.

2) Referring to current measurement value.

3) Temperature compensation can be switched off, without temperature compensation: 0.17 % / K.

4) Subsequent smoothing of the analog output, depending on the application, may increase the response time by up to 200 %.

Interfaces

Analog output Number 1 Type Current output / voltage output Function Automatic selection of analog current or voltage output dependent on load Current 4 mA ... 20 mA, ≤ 500 Ω 1) Voltage 0 V ... 10 V, ≥ 100,000 Ω Resolution 12 bit Multifunctional input (MF) 1 x MF

1) For 4 mA ... 20 mA and Vs ≤ 20 V max. load ≤ 100 Ω.

Ambient data

Ambient temperature, operation –25 °C ... +70 °C

Ambient temperature, storage –40 °C ... +85 °C