Resistance thermometer measuring transducer MCR-SL-PT100-UI-NC

Resistance thermometer measuring transducer MCR-SL-PT100-UI-NC
Resistance thermometer measuring transducer MCR-SL-PT100-UI-NC
  • MODEL: MCR-SL-PT100-UI-NC
  • LEAD TIME: IN STOCK
$76.00

Product data sheet

The narrow, 6.2 mm wide MINI MCR-SL-PT100-UI... is a configurable, 3-way isolated temperature transducer. It is suitable for connecting Pt 100 resistance thermometers in accordance with IEC 60751 in 2-, 3-, and 4-conductor connection technology.
Electrically isolated 0 ... 20 mA, 4 ... 20 mA, 0 ... 10 V, 0 ... 5 V, 1 ... 5 V, 10 ... 0 V, 20 ... 0 mA, or 20 ... 4 mA standard analog signals are available on the output side.
The DIP switches, which can be accessed on the side of the housing, are used to configure the following parameters:
- Connection technology
- Temperature range to be measured
- Output signal
- Type of error evaluation
Power (19.2 V DC to 30 V DC) can either be supplied via the connection terminal blocks of the modules or in conjunction with the DIN rail connector.


Electrical isolation 3-way isolation
Maximum power dissipation for nominal condition 235.5 mW
Protective circuit Transient protection
Step response (0–99%) < 160 ms
Maximum temperature coefficient < 0.02 %/K
Transmission error in the set measuring range ((100 K / set measurement range [K]) + 0.1)%
Transmission error in the full measuring range ≤ 0,2 %
Electrical isolation Input/output/power supply
Rated insulation voltage 50 V AC/DC
Test voltage 1.5 kV AC (50 Hz, 60 s)
Insulation Basic insulation in accordance with IEC/EN 61010
Supply
Nominal supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Max. current consumption < 21 mA (at 24 V DC)
Power consumption < 500 mW

Signal
Number of inputs 1
Measurement
Configurable/programmable Yes
Sensor types (RTD) that can be used Pt 100 (IEC 60751/EN 60751)
Temperature measuring range min. 50 K
Sensor type: -150 °C ... 850 °C (configurable)
Sensor input current 1 mA (constant)
Max. permissible overall conductor resistance 10 Ω (Per cable)
Connection technology 2-, 3-, 4-conductor

Signal: Voltage/current
Number of outputs 1
Configurable/programmable Yes, unconfigured
Voltage output signal 0 V ... 5 V
1 V ... 5 V
0 V ... 10 V
10 V ... 0 V
Max. voltage output signal  12.5 V
Non-load voltage  12.5 V
Current output signal 0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. current output signal 23 mA
Short-circuit current  10 mA
Load/output load voltage output ≥ 10 kΩ
Load/output load current output < 500 Ω (at 20 mA)
Ripple < 20 mVPP (at 10 kΩ)
< 20 mVPP (at 500 Ω)

Connection method Screw connection
Stripping length 12 mm
Screw thread M3
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 26 ... 12

Dimensional drawing
Width 6.2 mm
Height 93.1 mm
Depth 101.2 mm

Color green (RAL 6021)
Housing material PBT
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2

Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -20 °C ... 65 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 2000 m
Permissible humidity (operation) 5 % ... 95 % (non-condensing)

CE
Certificate CE-compliant
UKCA
Certificate UKCA-compliant
UL, USA/Canada
Identification UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
Shipbuilding approval
Certificate DNV GL TAA00002R0
DNV GL data
Temperature B
Humidity B
Vibration B
EMC A
Enclosure Required protection according to the Rules shall be provided upon installation on board

Noise immunity EN 61000-6-2
Note When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Comments Safety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 10 %
Fast transients (burst)
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 10 %
Surge current load (surge)
Standards/regulations EN 61000-4-5
Surge current load (surge)
Comments Criterion B
Conducted interference
Designation Conducted interferences
Standards/regulations EN 61000-4-6
Typical deviation from the measuring range final value 10 %

Electrical isolation 3-way isolation

Mounting type DIN rail mounting
Assembly note The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35 mm EN 60715 DIN rail.
Mounting position any
Product type Temperature transmitter
Product family MINI Analog
No. of channels 1
Configuration DIP switches
Insulation characteristics
Overvoltage category II
Pollution degree 2