Product characteristics
Number of inputs and outputs | Number of digital outputs: 1 |
---|
Measuring range | 0...250 bar | 0...3625 psi | 0...25 MPa |
|
---|
Process connection | threaded connection G 1/4 Internal thread |
---|
Application
System | gold-plated contacts |
---|
Application | for industrial applications |
---|
Media | liquids and gases |
---|
Conditionally suitable for | use in gases at pressures > 25 bar only on request |
---|
Medium temperature [°C] | -25...80 |
---|
Min. bursting pressure | |
---|
Pressure rating | |
---|
Type of pressure | relative pressure |
---|
Electrical data
Operating voltage [V] | 18...36 DC; (to SELV/PELV) |
---|
Current consumption [mA] | < 50 |
---|
Min. insulation resistance [MΩ] | 100; (500 V DC) |
---|
Protection class | III |
---|
Reverse polarity protection | yes |
---|
Overvoltage protection | yes; (< 40 V) |
---|
Power-on delay time [s] | 0.3 |
---|
Integrated watchdog | yes |
---|
Inputs / outputs
Number of inputs and outputs | Number of digital outputs: 1 |
---|
Outputs
Total number of outputs | 1 |
---|
Output signal | switching signal |
---|
Electrical design | PNP |
---|
Number of digital outputs | 1 |
---|
Output function | normally open / closed; (configurable) |
---|
Max. voltage drop switching output DC [V] | 2 |
---|
Permanent current rating of switching output DC [mA] | 250 |
---|
Switching frequency DC [Hz] | < 170 |
---|
Short-circuit protection | yes |
---|
Type of short-circuit protection | yes (non-latching) |
---|
Measuring/setting range
Measuring range | 0...250 bar | 0...3625 psi | 0...25 MPa |
|
---|
Set point SP | 2...250 bar | 40...3620 psi | 0.2...25 MPa |
|
---|
Reset point rP | 1...249 bar | 20...3600 psi | 0.1...24.9 MPa |
|
---|
In steps of | |
---|
Factory setting | |
---|
Accuracy / deviations
Switch point accuracy [% of the span] | < ± 0,5 |
---|
Repeatability [% of the span] | < ± 0,1; (with temperature fluctuations < 10 K) |
---|
Characteristics deviation [% of the span] | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
---|
Hysteresis deviation [% of the span] | < ± 0,25 |
---|
Long-term stability [% of the span] | < ± 0,05; (per 6 months) |
---|
Temperature coefficient zero point [% of the span / 10 K] | 0,2; (0...80 °C) |
---|
Temperature coefficient span [% of the span / 10 K] | 0,2; (0...80 °C) |
---|
Reaction times
Delay time programmable dS, dr [s] | 0; 0,2...50 |
---|
Software / programming
Parameter setting options | hysteresis / window; normally open / closed; switch-on/switch-off delay; Damping; Display unit |
---|
Operating conditions
Ambient temperature [°C] | -20...80 |
---|
Storage temperature [°C] | -40...100 |
---|
Protection | IP 67 |
---|
Tests / approvals
EMC | EN 61000-4-2 ESD | 4 kV CD / 8 kV AD | EN 61000-4-3 HF radiated | 10 V/m | EN 61000-4-4 Burst | 2 kV | EN 61000-4-5 Surge | 0,5/1 kV | EN 61000-4-6 HF conducted | 10 V |
|
---|
Shock resistance | DIN IEC 68-2-27 | 50 g (11 ms) |
|
---|
Vibration resistance | DIN IEC 68-2-6 | 20 g (10...2000 Hz) |
|
---|
Mechanical data
Weight [g] | 261.6 |
---|
Material | stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM |
---|
Materials (wetted parts) | stainless steel (1.4305 / 303); ceramics; FKM |
---|
Min. pressure cycles | 100 million |
---|
Process connection | threaded connection G 1/4 Internal thread |
---|
Displays / operating elements
Display | Display unit | 3 x LED, green | Switching status | LED, yellow | Function display | alphanumeric display, 4-digit | Measured values | alphanumeric display, 4-digit |
|
---|
Electrical connection
Connection | Connector: 1 x M12; coding: A; Contacts: gold-plated |
---|