Product data sheet
General Specifications
Switch Function Normally Open/Normally Closed (NO/NC)
Output type 2-wire type
Rated Working Distance 40 mm
Mounting Non-flush
Output polarity AC/DC
Ensured operating distance 0 ... 32,4 mm
Actual working distance 36 ... 44 mm Type 40 mm
Attenuation coefficient rAl 0,37
Attenuation factor rCu 0,3
Attenuation factor r304 0,73
Reduction factor rFe 1
Attenuation factor rBrass 0,4
Output type 2-wire
Nominal values
Switching frequency AC, 0 .... . 30 Hz
DC, 0 ... . 100 Hz
Hysteresis 1 ... 10 Type 5 %
Reverse polarity protection Reverse connection permitted
Short-circuit protection Pulsed
Voltage drop ≤ 5 V (2 V typical) DC operation
≤ 8 V (typ. 3 V) AC operation
Instantaneous current
(20 ms, 0.1 Hz) 0 ... 3000 mA
Operating current 5 ... 500 mA
Rated operating current 500 mA 50/60 Hz
Minimum operating current 5 mA
Breakdown current ≤ 1,5 mA
Usage categories AC12, AC140, DC12, DC13
Time delay before availability ≤ 300 ms
Operating voltage indicator Green LED
Switching status indicator Yellow LED
Error indicator Flashes in case of overcurrent
Functional safety-related parameters
MTTFd 540 a
Task time (TM) 20 a
Diagnostic coverage (DC) 0 %
Electrical specifications
Rated operating voltage 24 ... 250 V DC / 24 ... 230 V AC
Operating voltage 20 ... 275 V DC / 20 ... 253 V AC
Compliance with standards and directives
Compliance with standards
Standard EN IEC 60947-5-2
Approvals and certificates
Protection class II
Rated insulation voltage 250 V
Rated shock withstand voltage 2,5 kV
UL approvals cULus approvals, general purpose
"For NFPA 79 applications only".
Installation of an overcurrent protection fuse rated for a maximum current of 3 A and at least 300 V AC/DC
CCC certification Ue 75VDC - 250VDC Ue 75VAC - 230VAC
Ambient conditions
Ambient temperature -25 ... 85 °C (-13 ... 185 °F)
Storage temperature -25 ... 85 °C (-13 ... 185 °F)
Contamination level 3
Mechanical specifications
Connection type Terminal box
Connection information Up to two wires with the same core cross sectional area can be installed in one terminal connector!
Tightening torque 1.2 Nm + 10%
Cross-sectional area of cores up to 2.5 mm2
Minimum core cross-section without wire end collar 0,5 mm2 , with connector sleeve 0,34 mm2
Maximum core cross-section without wire end collar 2,5 mm2 , with connector sleeve 1,5 mm2
Housing material PA 6.6 / metal
Sensing surface PA 6.6
Housing base Plastic
Protection class IP67
Mass 255 g
Dimension
Height 40 mm
Width 40 mm
Length 118 mm
Tightening torque: 1.8 Nm (housing)