Product characteristics
Electrical design | PNP |
---|
Output function | normally open |
---|
Sensing range [mm] | 35 |
---|
Housing | rectangular |
---|
Dimensions [mm] | 40 x 40 x 54 |
---|
Electrical data
Operating voltage [V] | 10...36 DC |
---|
Current consumption [mA] | < 20 |
---|
Protection class | II |
---|
Reverse polarity protection | yes |
---|
Outputs
Electrical design | PNP |
---|
Output function | normally open |
---|
Max. voltage drop switching output DC [V] | 2.5 |
---|
Permanent current rating of switching output DC [mA] | 200 |
---|
Switching frequency DC [Hz] | 80 |
---|
Short-circuit protection | yes |
---|
Type of short-circuit protection | yes (non-latching) |
---|
Overload protection | yes |
---|
Monitoring range
Sensing range [mm] | 35 |
---|
Real sensing range Sr [mm] | 35 ± 10 % |
---|
Operating distance [mm] | 0...28.3 |
---|
Accuracy / deviations
Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminum: 0.4 / copper: 0.3 |
---|
Hysteresis [% of Sr] | 1...20 |
---|
Switch-point drift [% of Sr] | -10...10 |
---|
Operating conditions
Ambient temperature [°C] | -25...70 |
---|
Protection | IP 67 |
---|
Tests / approvals
EMC | EN 61000-4-2 ESD | 8 kV CD / 6 kV AD | EN 61000-4-3 HF radiated | 10 V/m | EN 61000-4-4 Burst | 2 kV | EN 61000-4-5 Surge | 0,5 kV line to line, Ri: 2 Ohm | EN 61000-4-6 HF conducted | 10 V | EN 55011 | class B |
|
---|
MTTF [years] | 1494 |
---|
UL approval | Ta | -25...70 °C | Enclosure type | Type 1 | voltage supply | Class 2 | File number UL | E174191 |
|
---|
Mechanical data
Weight [g] | 152.5 |
---|
Housing | rectangular |
---|
Sensing face | 5 positions selectable |
---|
Mounting | non-flush mountable |
---|
Dimensions [mm] | 40 x 40 x 54 |
---|
Material | PA |
---|
Displays / operating elements
Display | Switching status | 1 x LED, yellow | Power | 1 x LED, green |
|
---|
Electrical connection - plug
Connection | Connector: 1 x M12; coding: A; Locking: locking, rotatable |
---|