Product data sheet
Number of inputs and outputs | Number of digital outputs: 2 |
---|---|
Factory setting | automatic medium detection |
Probe length L [mm] | 472 |
Application
System | gold-plated contacts |
---|---|
Media | hydrous coolants; oils; oil-based media; water; media similar to water |
Dielectric constant of the medium | > 2 |
Cannot be used for | extremely conductive media; adhering media; granulates; bulk material; acids; alkali; hygienic areas and electroplating applications |
Maximum speed of the change of level [mm/s] | 200 |
Tank pressure [bar] | 0.5; (when mounting with mounting accessories: E43001 - E43007, E43019) |
Coolants
Medium temperature [°C] | 0...35; (with climate tube E43101: 35...60 °C) |
---|
Oil
Medium temperature [°C] | 0...70 |
---|---|
Medium temperature short time [°C] | 0...90; (< 1 h) |
Water
Medium temperature [°C] | 0...35; (with climate tube E43101: 35...60 °C) |
---|
Electrical data
Operating voltage [V] | 12...30 DC |
---|---|
Current consumption [mA] | < 50 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | < 3 |
Measuring principle | capacitive |
Inputs / outputs
Number of inputs and outputs | Number of digital outputs: 2 |
---|
Outputs
Total number of outputs | 2 |
---|---|
Output signal | switching signal; IO-Link |
Electrical design | PNP/NPN |
Number of digital outputs | 2 |
Output function | normally open / closed; (configurable) |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 200 |
Short-circuit protection | yes |
Type of short-circuit protection | thermal, pulsed |
Overload protection | yes |
Measuring/setting range
Factory setting | automatic medium detection |
---|---|
Probe length L [mm] | 472 |
Active range A [mm] | 390 |
Inactive range I1 / I2 [mm] | 60 / 22 |
Tags:
ZORX-CJ24081902