Product data sheet
Input
Input Voltage • 90-132/180-264 VAC, auto select,
210-375 VDC (DNR120AS, DNR240PS)
90-264 VAC, 120-375 VDC (DNR480PS)
Input Frequency • 47-63 Hz
Input Current • See tables
Inrush Current • 24/48 A at 115/230 VAC (DNR120)
30/60 A at 115/230 VAC (DNR240)
25/50 A at 115/230 VAC (DNR480)
Power Factor • 0.7 typical (DNR120, DNR240)
0.9 typical (DNR480)
Earth Leakage Current • 0.8 mA max
Input Protection • T3.15A, 250 VAC (DNR120)
T6.3A, 250 VAC (DNR240)
T10A, 250 VAC (DNR480
Output
Output Voltage • See tables
Output Voltage Trim • See tables
Initial Set Accuracy • ±1%
Minimum Load • No minimum load required
Start Up Delay • <1 s (may increase at low
temperature extremes)
Start Up Rise Time • <150 ms
Hold Up Time • 25/30 ms at 115/230 VAC
Line Regulation • ±0.5% max
Load Regulation • ±1% (±5% for units in parallel)
Parallel Operation • A maximum of 3 units can be paralleled
(not with standby system). Total power
available is 90% of the rated current of
each unit. Minimum load per unit 10%
Transient Response • 4% max deviation recovering to within
1% in 2 ms for a 50% load change
Ripple & Noise • 50 mV pk-pk (DNR120)
100 mV pk-pk (DNR240, DNR480)
20 MHz bandwidth (may increase at low
temperature extremes)
Overvoltage Protection • Output clamps at 125-140% Vnom,
auto recovery
Overload Protection • 105-145% constant current, auto recovery
120-165% contstant current (DNR240)
Temp. Coefficient • ±0.03%/°c
General
Efficiency • See table
Isolation • 3000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
Switching Frequency • See table
Signals • DC ON indicator Green LED,
DC LOW indicator Red LED
DC OK: 24 V and standby models
MTBF • 430 kHrs typical Bellcore,
Issue 6 at +40 °C, GB
DIN Rail • Compatible with TS35/7.5 or TS35/15
Environmental
Operating Temperature • DNR120: -35 °C to +70 °C, derate linearly
from +60 °C at 2.5%/°C, start up at -30 °C
DNR240: -40 °C to +70 °C, derate linearly
from +60 °C at 2.5%/°C, start up at -35 °C
DNR480: -40 °C to +70 °C, derate linearly
from +55 °C at 2.5%/°C, start up at -35 °C
(see derating curves)
Cooling • Convection-cooled with 25mm free space
all sides
Operating Altitude • 5000m
Operating Humidity • 20-95% RH, non-condensing
Storage Temperature • -40 °C to +85 °C
Shock • 15 g, 11 ms, 3 axes, 6 faces, 3 shocks
per face
Vibration • 2 g, 10 Hz to 500 Hz, along X, Y & Z axis,
60 min/axis, mounted on rail
EMC & Safety
Emissions • EN55022, class B conducted & radiated
Harmonic Currents • EN61000-3-2, class A
Voltage Flicker • EN61000-3-3
ESD Immunity • EN61000-4-2, level 4 Perf Criteria A
Radiated Immunity • EN61000-4-3, level 3 Perf Criteria A
EFT/Burst • EN61000-4-4, level 4 Perf Criteria A
Surge • EN61000-4-5, installation class 3,
Perf Criteria A
Conducted Immunity • EN61000-4-6, level 3 Perf Criteria A
Magnetic Field • EN61000-4-8, level 4 Perf Criteria A
Dips & Interruptions • EN61000-4-11, 30% 10 ms,
60% 100 ms, 100% 5000 ms
Perf Criteria A, A, B
Safety Approvals • EN62368-1, UL508, UL62368-1,
cUL60950-1, Pollution Degree 2, CE Mark,
UL60950-1, Overvoltage Category II,
UL508 Overvoltage Category III, ANSI/ISA
12.12.01. (Class 1, Division 2 Groups A, B,
C and D), CE & UKCA meets all applicable
directives & legislation