Product data sheet
General specifications
Ambient temperature | ||
Ambient humidity | ||
Vibration resistance | Installed on DIN rail | Frequency: 10 to 57 Hz |
Frequency: 57 to 150 Hz | ||
Direct installing | Frequency: 10 to 57 Hz | |
Frequency: 57 to 150 Hz | ||
Shock resistance | ||
Noise resistance | ||
Dielectric withstand voltage | ||
Insulation resistance | ||
Grounding | ||
Working atmosphere | ||
Working altitude |
0 to 55°C (32 to 131°F) when operating and -25 to 75°C (-13 to 167°F) when stored |
5 to 95%RH (no condensation) when operating |
Half amplitude: 0.035mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2. |
Acceleration: 4.9 m/s2 Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2. |
Half amplitude: 0.075 mm Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2. |
Acceleration: 9.8 m/s2 Sweep Count for X, Y, Z: 10 times (80 min in each direction) The criterion is shown in IEC61131-2. |
147 m/s2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z The criterion is shown in IEC61131-2. |
By noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 μs, rise time of 1 ns and period of 30 to 100 Hz |
Perform dielectric withstand voltage test at the following voltage between each terminals and the main unit ground terminal. Between power supply terminal (DC power supply) and ground terminal: 500 V AC for 1 min Between output terminal (transistor) and ground terminal: 500 V AC for 1 min |
Perform insulation resistance test at the following voltage between each terminals and the main unit ground terminal. Between power supply terminal (DC power supply) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester Between output terminal (transistor) and ground terminal: 5 MΩ or higher by 500 V DC insulation resistance tester |
Class D grounding (grounding resistance: 100 Ω or less) (Common grounding with a heavy electrical system is not allowed) Ground the PLC independently or jointly. |
Free from corrosive or flammable gas and excessive conductive dusts |
2000 m or less Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may damage the PLC. |