Product data sheet
Primary voltage limit 85...264 V
Network Frequency 50/60 Hz
network frequency limits 47…63 Hz
Apparent power 0.07 kVA
Input current 0.31 A 240 V
0.61 A 115 V
Inrush current 30 A 120 V
60 A 240 V
I²t on activation 12 A².s 240 V
It on activation 0.06 A.s 240 V
0.03 A.s 120 V
MTBF reliability 4638000 H
Protection type Internal fuse not accessible primary circuit
Overload protection secondary circuit
Overvoltage protection secondary circuit
Short-circuit protection secondary circuit
Current at secondary voltage 0.45 A 24 V DC sensor power supply
0.7 A 24 V DC I/O module power supply and processor
2.5 A 3.3 V DC I/O module logic power supply
Maximum power dissipation in W 8.5 W
Status LED 1 LED (Green) rack voltage OK
1 LED (Green) sensor voltage
Control Type RESET push-button cold restart
Electrical connection 1 connector 2 alarm relay
1 connector 5 line supply, protective earth, 24 V DC input sensor
Insulation resistance >= 100 MOhm primary/ground
>= 100 MOhm primary/secondary
Net Weight 0.7 lb(US) (0.3 kg)