Modular surge arrester A9L65601

Modular surge arrester A9L65601
Modular surge arrester A9L65601
  • MODEL: A9L65601
  • Weight: 0.50kg
  • LEAD TIME: 1-2 weeks
$327.00

Product data sheet

Main
range of productActi9
Product nameActi9 iPRD
product or component typeSurge arrester with pluggable cartridge
Device short nameiPRD65r
Device applicationDistribution
StandardsEN 61643-11:2012
IEC 61643-11:2011
Product certificationsCE
Quality labelsNF
KEMA-KEUR
poles description3P + N
Remote signallingWith
Signal contacts composition1 SD (1 C/O)
Surge arrester typeElectrical distribution network
Earthing systemTN-S
TT

Complementary
Surge arrester class typeType 2
Surge arrester technologyMOV + GDT
[Ue] rated operational voltage230/400 V AC (+/- 10 %) at 50/60 Hz
[In] nominal discharge currentCommon mode: 20 kA (L/PE)
Common mode: 20 kA (N/PE)
Differential mode: 20 kA (L/N)
[Imax] maximum discharge currentCommon mode: 65 kA L/PE
Common mode: 65 kA N/PE
Differential mode: 65 kA L/N
[Uc] maximum continuous operating voltageCommon mode: 260 V N/PE
Common mode: 350 V L/PE
Differential mode: 350 V L/N
Maximum [Up] voltage protection levelCommon mode <1.5 kV type 2 N/PE
Differential mode <1.5 kV type 2 L/N
[Ut] temporary overvoltage337 V L/N 5 s withstand
1200 V N/PE 200 ms safe failure mode
442 V L/PE 5 s withstand
1453 V L/PE 200 ms safe failure mode
Disconnector device typeAssociated circuit breaker IC60N 50 A curve C - Icu 10 kA
Associated circuit breaker iC60H 50 A curve C - Icu 15 kA
Associated circuit breaker NG125N 50 A curve C - Icu 25 kA
Associated circuit breaker NG125H 50 A curve C - Icu 36 kA
Associated circuit breaker NG125L 50 A curve C - Icu 50 kA
Associated fuse gG 80 A - Icu 50 kA
Signalling circuit voltage0.25 A/250 V AC 50/60 Hz
Mounting modeClip-on (DIN rail)
9 mm pitches8
Height85 mm
Width72 mm
Depth69 mm
net weight0.492 kg
ColourWhite (RAL 9003)
[Ipe] Ground residual current0.003 mA
0.6 mA
Connections - terminalsTunnel type terminal (downside) 2.5…35 mm²
Tunnel type terminal (upside) 2.5…35 mm²
Tightening torque2.5 N.m

Environment
IK degree of protectionIK03 conforming to IEC 62262
Relative humidity5…95 %
Operating altitude2000 m
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-40…85 °C