Product characteristics
Output function | normally open / closed; (selectable) |
---|
Sensing range [mm] | 10 |
---|
Housing | tubular |
---|
Dimensions [mm] | Ø 20 / L = 92 |
---|
Electrical data
Operating voltage [V] | 20...250 AC/DC |
---|
Protection class | II |
---|
Reverse polarity protection | no |
---|
Outputs
Output function | normally open / closed; (selectable) |
---|
Max. voltage drop switching output DC [V] | 6 |
---|
Max. voltage drop switching output AC [V] | 6.5 |
---|
Minimum load current [mA] | 5 |
---|
Max. leakage current [mA] | 2.5 (250 V AC) / 1.3 (110 V AC) / 0.8 (24 V DC) |
---|
Permanent current rating of switching output AC [mA] | 250; (350 (...50 °C)) |
---|
Permanent current rating of switching output DC [mA] | 100 |
---|
Short-time current rating of switching output [mA] | 2200; (20 ms / 0,5 Hz) |
---|
Switching frequency AC [Hz] | 25 |
---|
Switching frequency DC [Hz] | 70 |
---|
Short-circuit proof | no |
---|
Overload protection | no |
---|
Monitoring range
Sensing range [mm] | 10 |
---|
Real sensing range Sr [mm] | 10 ± 10 % |
---|
Operating distance [mm] | 0...8.1 |
---|
Accuracy / deviations
Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminum: 0.3 / copper: 0.2 |
---|
Hysteresis [% of Sr] | 1...15 |
---|
Switch-point drift [% of Sr] | -10...10 |
---|
Operating conditions
Ambient temperature [°C] | -25...80 |
---|
Protection | IP 65 |
---|
Tests / approvals
EMC | EN 60947-5-2 | | EN 55011 | class B |
|
---|
MTTF [years] | 606 |
---|
UL approval | Ta | 0...40 °C | Enclosure type | Type 1 | voltage supply | Hazardous voltage | File number UL | E174191 |
|
---|
Mechanical data
Weight [g] | 83.5 |
---|
Housing | tubular |
---|
Mounting | non-flush mountable |
---|
Dimensions [mm] | Ø 20 / L = 92 |
---|
Material | PBT; LED window: PC |
---|
Displays / operating elements
Display | Switching status | 1 x LED, yellow |
|
---|
Electrical connection
Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting |
---|
Remarks
Remarks | Recommendation: check the unit for reliable function after a short circuit. |
|
---|
Pack quantity | 1 pcs. |
---|
Electrical connection
Connection | terminals: ...2.5 mm²; Cable sheath: Ø 4.5...10 mm; Cable gland: M16 X 1.5 |
---|