Product data sheet
Technical Data
Programming interface programming socket
Input
Connection side field side
Connection Input I: intrinsically safe: terminals 1+, 3-
Input II: non-intrinsically safe: terminals 13+, 14-
Input I sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Pulse duration > 50 µs
Input frequency 0.001 ... 5000 Hz
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input II startup override: 1 ... 1000 s, adjustable in steps of 1 s
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit current 18 V / 5 mA
Output
Connection side control side
Connection output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
outout III: terminasl 19+, 20-
output IV: terminals 8+, 7-
Output I, II signal, relay
Contact loading 253 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
Mechanical life 5 x 107 switching cycles
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Output III electronic output, passive
Contact loading 40 V DC
Signal level 1-signal: (L+) - 2.5 V (50 mA, short-circuit/overload proof)
0-signal: switched off (off-state current ≤ 10 µA)
Output IV analog
Current range 0 ... 20 mA or 4 ... 20 mA
Open loop voltage max. 24 V DC
Load max. 650 Ω
Fault signal downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
Collective error message Power Rail
Transfer characteristics
Input I
Measurement range 0.001 ... 5000 Hz
Resolution 0.1 % of the measurement value , ≥ 0.001 Hz
Accuracy 0.1 % of the measurement value , > 0.001 Hz
Measuring time < 100 ms
Influence of ambient temperature 0.003 %/K (30 ppm)
Output I, II
Response delay ≤ 200 ms
Output IV
Resolution < 10 µA
Accuracy < 20 µA
Influence of ambient temperature 0.005 %/K (50 ppm)
Galvanic isolation
Input I/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/power supply and collective error basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III/start-up override basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III/IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output IV/power supply and collective error functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Start-up override/power supply and collective
error
functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff