Product data sheet
Range of product | EOCR |
---|---|
Device short name | EOCR-3D420 |
product or component type | Protection relay |
Protection type | Overload, In > OC setting Sensitivity to phase loss Sensitivity to phase reverse Locked rotor, In > 3 times OC setting Phase unbalance, 50 % |
Product specific application | Overcurrent protection |
Analogue output range | 4...20 mA |
Network type | AC |
Network frequency | 50...60 Hz |
protection ajustment range | 0.5…10 A |
Tripping threshold | 0.5...6 A |
[Us] rated supply voltage | 220 V AC |
---|---|
Mounting support | 35 mm DIN rail Panel |
Contacts type and composition | 1 NO + 1 NC (OL) |
Short-circuit and overload protection | By 4 A gG fuse |
[Ue] rated operational voltage | 600 V AC 50...60 Hz for power circuit conforming to UL 690 V AC 50...60 Hz for power circuit conforming to CSA 690 V AC 50...60 Hz for power circuit conforming to IEC 60947-4-1 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-4-1 |
Reset | Manual reset Electrical 0…1 s by interruption of power supply |
Time delay type | O-Time: 0.3, 1...30 s, off (definite) D-Time: 1...120 s, off (definite) O-Time: 1...30 class (inverse) D-Time: 0...120 s (inverse) |
Display type | 7 segments LED |
power consumption per relay | 3 W |
Connections - terminals | Control circuit: cable 2 x 1…1.5 mm²flexible with cable end - M3 Control circuit: cable 2 x 1…1.5 mm²flexible without cable end - M3 Control circuit: cable 1 x 1…2.5 mm²flexible with cable end - M3 Control circuit: cable 1 x 1…2.5 mm²flexible without cable end - M3 |
Tightening torque | Control circuit: 0.8...1.2 N.m on cable, 4.7 mm |
Height | 71 mm |
Width | 70 mm |
Depth | 68 mm |
net weight | 0.325 kg |
Standards | IEC 60947-4-1 |
---|---|
IP degree of protection | IP20 conforming to IEC 60529 |
Ambient air temperature for operation | -20…60 °C conforming to IEC 60947-4-1 |
Ambient air temperature for storage | -30…80 °C |
Operating altitude | 2000 m |
Fire resistance | 650 °C conforming to IEC 60695-2-12 960 °C conforming to UL 94 |
Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-7 |
Vibration resistance | 4 gn on panel mounting conforming to IEC 60068-2-6 2 gn on 35 mm DIN rail conforming to IEC 60068-2-6 |
Dielectric strength | 2 kV 50...60 Hz in between case and circuit conforming to IEC 60255-5 1 kV 50...60 Hz in between contact conforming to IEC 60255-5 2 kV 50...60 Hz in between circuit conforming to IEC 60255-5 |
Surge withstand | 6 kV conforming to IEC 61000-4-5 |
Electromagnetic compatibility | Resistance to radiated electromagnetic fields: 10 V/m level 3 conforming to IEC 61000-4-3 Resistance to electrostatic discharge: 8 kV air, 6 kV contact conforming to IEC 61000-4-2 Resistance to fast transient: 2 kV conforming to IEC 61000-4-4 Conducted RF disturbances: 10 V conforming to EN 61000-4-6 Conducted RF disturbances: class A conforming to EN 55011 |
[Ith] conventional free air thermal current | 5 A for control circuit |
Permissible current | 250 V, 5 A AC |
Tags: