Product data sheet
Range of product | Harmony XAC |
---|---|
product or component type | Contact block |
Component name | XENG |
Electrical circuit type | Control circuit |
Contact block application | 2-speed |
Contact block type | Single |
Type of operator | Spring return |
Product compatibility | XACA XACA9...head |
Contacts type and composition | 1 NC + 2 NO |
Mounting of block | Front mounting |
Contact operation | Slow-break Staggered |
Connections - terminals | Screw clamp terminals, 1 x 0.5...1 x 2.5 mm² without cable end Screw clamp terminals, 1 x 0.5...2 x 1.5 mm² with cable end |
---|---|
Mechanical durability | 1000000 cycles |
Contact code designation | A600 AC-15, Ue = 240 V, Ie = 3 A conforming to IEC 60947-5-1 appendix A A600 AC-15, Ue = 600 V, Ie = 1.2 A conforming to IEC 60947-5-1 appendix A Q600 DC-13, Ue = 250 V, Ie = 0.27 A conforming to IEC 60947-5-1 appendix A Q600 DC-13, Ue = 600 V, Ie = 0.1 A conforming to IEC 60947-5-1 appendix A |
[Ithe] conventional enclosed thermal current | 10 A |
[Ui] rated insulation voltage | 600 V (pollution degree 3) conforming to IEC 60947-1 |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-1 |
Maximum resistance across terminals | 25 MOhm |
Operating force | 18 N |
Short-circuit protection | 10 A fuse protection by cartridge fuse type gG |
Rated operational power in W | 40 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 120 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C 48 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 48 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C 65 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 24 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C |
Terminals description ISO n°1 | (21-22)NC (33-34)NO_CL (13-14)NO |
net weight | 0.04 kg |