Product data sheet
Customs Tariff Number:
85371091
Popular Downloads
Data Sheet, Technical Information:
Instructions and Manuals:
CAD Dimensional Drawing:
Wiring Diagram:
Dimensions
Product Net Width:
258 mm
Product Net Height:
470 mm
Product Net Depth / Length:
279 mm
Product Net Weight:
15.5 kg
Technical
Rated Operational Voltage:
208 ... 600 V AC
Rated Control Supply Voltage (Us):
100 ... 250 V AC
Rated Control Circuit Voltage (Uc):
24 V DC
Rated Frequency (f):
50/60 Hz
Main Circuit 50 / 60 Hz
Rated Operational Power - In-Line Connection (Pe):
(230 V) 90 kW
(400 V) 160 kW
(500 V) 200 kW
Rated Operational Current - In-Line Connection (Ie):
300 A
Rated Operational Power - Inside Delta Connection:
at 230 V 160 kW
at 400 V 257 kW
at 500 V 355 kW
Rated Operational Current - Inside Delta Connection:
515 A
Service Factor Percentage:
100 %
Overload Protection:
Built-in electronic overload protection
Integrated Electronic Overload:
Yes
Adjustable Rated Motor Current Ie:
30 ... 100 %
Starting Capacity at Maximum Rated Current Ie:
4xIe for 10s
Ramp Time:
1 ... 120 second [unit of time]
Initial Voltage During Start:
30 ... 99 %
Step Down Voltage Special Ramp:
100 ... 10 %
Current Limit Function:
1.5 ... 7.5 xle
Switch for Inside Delta Connection:
Yes
Run Signal Relay:
Yes
By-pass Signal Relay:
Yes
Fault Signal Relay:
Yes
Overload Signal Relay:
Yes
Analog Outputs:
0…10 V, 0…20 mA, 4…20 mA
Signal Indication Ready to Start/Standby ON (LED):
Green
Signal Indication Running R (LED):
Green
Signal Indication Protection (LED):
Yellow
Signal Indication Fault (LED):
Red&
Tags:
HDL-NS24080801