Product data sheet
General information
Product type designation AQ 8xU/I HS
HW functional status FS01
Firmware version V2.1.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Prioritized startup No
● Output range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated as of
version
V14 / -
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PROFIBUS as of GSD version/GSD revision V1.0 / V5.1
● PROFINET as of GSD version/GSD revision V2.3 / -
Operating mode
● Oversampling Yes
● MSO Yes
CiR – Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Type of supply voltage DC
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 260 mA; with 24 V DC supply
Power
Power available from the backplane bus 1.15 W
Power loss
Power loss, typ. 7 W
Analog outputs
Number of analog outputs 8
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 45 mA
Current output, no-load voltage, max. 20 V
Cycle time (all channels), min. 125 µs; independent of number of activated channels
Output ranges, voltage
● 0 to 10 V Yes
● 1 V to 5 V Yes
● -5 V to +5 V No
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Connection of actuators
● for voltage output two-wire connection Yes
● for voltage output four-wire connection Yes
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ
● with voltage outputs, capacitive load, max. 100 nF
● with current outputs, max. 500 Ω
● with current outputs, inductive load, max. 1 mH