Product data sheet
Areas of application for contactors Used in non-inductive or slightly inductive loads, resistance furnaces
For AC loads with a power factor greater than or equal to 0.95.
Category of use AC-4
AC-1
AC-3
AC-3e
Number of poles 3P
Rated operating voltage [Ue] Power circuit: <= 690 V AC 25...400 Hz. .400 Hz
Power circuit: <= 300 V DC
Rated operating current [Ie] 50 A (at operating temperature <= 60 °C) at operating voltage <= <= 440 V AC AC-3 for power supply circuits
80 A (at operating temperatures <= 60 °C) at operating voltages <= <= 440 V AC AC-1 for power circuits
50 A (at operating temperature <= 60 °C) when operating voltage <= <= 440 V AC AC-3e for power supply circuits
[Uc] control circuit voltage 220 V AC 50/60 Hz
Additional information
Motor power (kW) 15 kW When operating voltage <= 220.... .230 V AC 50/60 Hz (AC-3)
22 kW when operating voltage <= 380.... .400 V AC 50/60 Hz (AC-3)
30 kW at operating voltages <= 500 V AC 50/60 Hz (AC-3)
33 kW when operating voltage <= 660... .690 V AC 50/60 Hz (AC-3) .690 V AC 50/60 Hz (AC-3)
25 kW at operating voltages <= 415 V AC 50/60 Hz (AC-3)
30 kW at operating voltage <= 440 V AC 50/60 Hz (AC-3)
11 kW at operating voltage <= 400 V AC 50/60 Hz (AC-4)
15 kW at operating voltages <= 220....230 V AC 50/60 Hz (AC-4) .230 V AC 50/60 Hz (AC-3e)
22 kW at operating voltages <= 380... .400 V AC 50/60 Hz (AC-3e) .400 V AC 50/60 Hz (AC-3e)
30 kW at operating voltages <= 500 V AC 50/60 Hz (AC-3e)
33 kW at operating voltages <= 660... .690 V AC 50/60 Hz (AC-3e) .690 V AC 50/60 Hz (AC-3e)
25 kW at operating voltages <=415 V AC 50/60 Hz (AC-3e)
30 kW at operating voltage <= 440 V AC 50/60 Hz (AC-3e)
Motor power 3 hp at operating voltage <= 115 V AC 50/60 Hz for 1-phase motors
7.5 hp at operating voltage <= 230/240 V AC 50/60 Hz for 1-phase motors
15 hp when operating voltage <= 200/208 V AC 50/60 Hz for 3-phase motors
15 hp when operating voltage <= 230/240 V AC 50/60 Hz for 3-phase motors
40 hp when operating voltage <= 460/480 V AC 50/60 Hz for 3-phase motors
40 hp at operating voltage <= 575/600 V AC 50/60 Hz for 3-phase motors
Model LC1D
Circuit contact type 3 NO
Protective cover with
Conventional heating current [Ith] 10 A (at operating temperature <= 60 °C) for signaling circuits
80 A (at operating temperatures <=60 °C) for power supply circuits
Product data sheet
Specification
Rated turn-on capacity [Irms] 140 A AC for signal circuits according to IEC 60947-5-1
250 A DC for signaling circuits in accordance with IEC 60947-5-1
900 A at operating voltage <= 440 V for power circuits in accordance with IEC 60947
Rated breaking capacity 900 A at operating voltage <= 440 V for power circuits in accordance with IEC 60947
Rated short-time withstand current [Icw] 400 A at operating temperature <= 40 °C for 10 s for power circuits
810 A at operating temperature <= 40 °C
84 A at operating temperatures <= 40 °C for 10 minutes for power circuits
208 A for 1 min at operating temperatures <= 40 °C for power circuits
100 A for 1 s for signaling circuits
120 A for 500 ms for signaling circuits
140 A for 100 ms for signal circuits
Fuses for use with relays 10 A gG for signal circuits in accordance with IEC 60947-5-1
100 A gG at operating voltages <=<= 690 V in conjunction with type 1, for power circuits
100 A gG at operating voltages <=<= 690 V with type 2, for power circuits
Average impedance 1.5 mΩ - Ith 80 A 50 Hz for power circuits
Power consumption per pole 3.7 W AC-3
9.6 W AC-1
3.7 W AC-3e
Rated insulation voltage [Ui] Power supply circuit: 600 V CSA approved
Power supply circuit: 600 V UL recognized
Signal circuit: 690 V in accordance with IEC 60947-1
Signal circuit: 600 V CSA approved
Signal circuits: 600 V UL recognized
Power circuits: 690 V according to IEC 60947-4-1
Overvoltage category III
Pollution class 3
Rated impulse withstand voltage [Uimp] 6 kV according to IEC 60947
Safety and reliability class B10d = 1369863 cycles Contactor with nominal load in accordance with EN/ISO 13849-1
B10d = 20000000 cycles Contactors for mechanical loads in accordance with EN/ISO 13849-1
Mechanical life 6 Mcycles
Electrical life 1.45 Mcycles 50 A AC-3 Ue <= 440 V
1.1 Mcycles 80 A AC-1 Ue <= 440 V
1.45 Mcycles 50 A AC-3e Ue <= 440 V
Control loop characteristics AC at 50/60 Hz Standard
Surge suppression module No built-in surge suppression module
Control voltage limits 0.3.... .0.6 Uc (-40...70 °C) Coil release AC 50/60 Hz
0.8... .1.1 Uc (-40...70 °C) .1.1 Uc (-40...60 °C) Coil release AC 50 Hz
0.85... .1.1 Uc (-40...60 °C) .1.1 Uc (-40...60 °C Coil suction AC 60 Hz)
1... .1.1 Uc (-40...60 °C) .1.1 Uc (60...70 °C Coil suction AC 50/60 Hz)
(Power consumption (VA) 140 VA 60 Hz cos phi 0.75 (at 20°C)
160 VA 50 Hz cos phi 0.75 (at 20 °C)
(~50 Hz Hold) Power Consumption (VA) 13 VA 60 Hz cos phi 0.3 (at 20 °C)
15 VA 50 Hz cos phi 0.3 (at 20 °C)
Thermal dissipation 4...5 W at 50/60 Hz
Operating time 4... .19 ms .19 ms breaking
12... .26 ms Closing 12...26 ms closing
Max. operating frequency 3600 operations/h at 60 °C
Control circuits: screwed 2 1...2.5 mm² Cable type: flexible cord with terminal block
Control circuits: screwed 1 1...4 mm² Cable type: flexible cord without terminals
Control circuits: screw fastening 2 1...4 mm² Cable type: cord without terminals
Control circuits: screwed 1 1...4 mm² Cable type: cord with terminals
Control circuits: screw fastening 1 1...4 mm² Cable type: hardwire without terminals
Control circuits: screw fastening 2 1...4 mm² Cable type: hardwire without terminals
Power supply circuits: EverLink BTR terminal block 1 1...35 mm² Cable type: flexible cord without terminal block
Power supply circuits: EverLink BTR terminal block 2 1...25 mm² Cable type: Flex cable with terminal block
Power supply circuit: EverLink BTR terminal block 1 1...35 mm² Cable type: Hardwire without terminal block
Power supply circuits: EverLink BTR terminal block 2 1...25 mm² Cable type: Hardwire without terminal block
Tightening torque Control circuits: 1.7 N.m via EverLink BTR terminal block with screwdriver Ø 6 flat
Control circuit: 1.7 N.m via EverLink BTR terminal blocks with screwdriver No 2 Phillips screws
Power supply: 8 N.m via EverLink BTR terminal blocks Cable 25...35 mm² hexagonal 4 mm
Power supply circuit: 5 N.m via EverLink BTR terminal block cable 1...25 mm² hexagonal 4 mm
Control circuit: 1.7 N.m via EverLink BTR terminal blocks with screwdriver pozidriv No 2
Power supply circuit: 2.5 N.m via EverLink BTR terminal block with screwdriver pozidriv No 2
Auxiliary contact type 1 NO + 1 NC
Auxiliary contact type Type Mechanical connection 1 NO + 1 NC in accordance with IEC 60947-5-1
Type Mirrored to the state of the main contact 1 NC in accordance with IEC 60947-4-1
Signal circuit frequency 25.... .400 Hz
Minimum switching voltage 17 V for signal circuits
Minimum switching current [Imin] 5 mA for signaling circuits
Insulation resistance > 10 MΩ for signal circuits
Non-repeat time 1.5 ms Power loss between NC and NO contacts
1.5 ms Between NC and NO contacts for power gain
Mounting method Base plate mounting
Rail mounting
Standard CSA C22.2 No.
Standard CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1
Product certificates RINA
DNV
CSA
GOST
BV
GL
UL
CCC
LROS (Lloyds register of shipping)
IP protection class IP20 Front panel according to IEC 60529
Protective measures TH in accordance with IEC 60068-2-30
Weather resistance Conforms to IACS E10 Exposure to hot and humid conditions
Conforms to IEC 60947-1 Annex Q category D for exposure to hot and humid conditions.
Ambient air temperature -40...60 °C
60...70 °C with reduced capacity
Operating altitude 0...3000 m ...3000 m
Fire resistance and resistance to abnormally high temperatures 850 °C according to IEC 60695-2-1
Flame retardant V1 according to UL 94
Shock and vibration resistance Vibration resistance Contact opening (2 gn (5...300 Hz)) . 300 Hz))
Vibration Resistant Contact closure (4 gn (5...300 Hz)) .300 Hz))
Shock resistance with contact closed (15 gn (11ms))
Shock resistance with open contact (10 gn (11ms))
Height 122 mm
Width 55 mm
Depth 120 mm
Net weight 0.855 kg