Main
Range TeSys
Device short name GV4AE
Product or Component Type Auxiliary contact
Device Application Signalling
Range compatibility TeSys TeSys GV4
TeSys TeSys BV4
Auxiliary contact composition 1 NO/NC
[Ue] rated operational voltage <= 690 V
[Ith] conventional free air thermal
current
5 A IEC 60947-5-1
5 A CSA C22.2 No 14
5 A UL 508
Mounting Mode Internal mounting
Complementary
[Ui] rated insulation voltage 690 V IEC 60947-1
[Ie] rated operational current 5 A <= 690 V AC-12 IEC 60947-5-1
5 A <= 48 V AC-15 IEC 60947-5-1
4 A 110/127 V AC-15 IEC 60947-5-1
3 A 220/240 V AC-15 IEC 60947-5-1
2.5 A 380...440 V AC-15 IEC 60947-5-1
0.11 A 660/690 V AC-15 IEC 60947-5-1
5 A <= 24 V DC-12 IEC 60947-5-1
2.5 A 48 V DC-12 IEC 60947-5-1
0.6 A 110/127 V DC-12 IEC 60947-5-1
0.3 A 250 V DC-12 IEC 60947-5-1
2.5 A <= 24 V DC-12 IEC 60947-5-1
1.2 A 48 V DC-12 IEC 60947-5-1
0.35 A 110/127 V DC-12 IEC 60947-5-1
0.05 A 250 V DC-12 IEC 60947-5-1
1 A <= 24 V DC-12 IEC 60947-5-1
0.2 A 48 V DC-12 IEC 60947-5-1
0.05 A 110/127 V DC-12 IEC 60947-5-1
0.03 A 250 V DC-12 IEC 60947-5-1
Rated power in VA 120 VA AC-12 24 V IEC 60947-5-1
240 VA AC-12 48 V IEC 60947-5-1
635 VA AC-12 110/127 V IEC 60947-5-1
1200 VA AC-12 230/240 V IEC 60947-5-1
2200 VA AC-12 380/440 V IEC 60947-5-1
3450 VA AC-12 660/690 V IEC 60947-5-1
Rated power in W DC-12 120 W 24 V IEC 60947-5-1
DC-12 120 W 48 V IEC 60947-5-1
DC-12 66 W 110 V IEC 60947-5-1
DC-12 75 W 250 V IEC 60947-5-1
Associated fuse rating 5 A gG at 690 V conforming to IEC 60947-5-1
Minimum switching current 2 mA
Minimum switching voltage 17 V
Mechanical durability 40000 cycles
Connections - terminals Spring terminals 1 0.0008…0.002 in² (0.5…1.5 mm²) - cable stiffness: flexible without
cable end
Wire stripping length 0.3 in (8 mm)
Environment
Quantity per Set Set of 1