Product data sheet
General technical data
size of contactor S0
product extension
● function module for communication No
● auxiliary switch Yes
power loss [W] for rated value of the current
● at AC in hot operating state 5.7 W
● at AC in hot operating state per pole 1.9 W
● without load current share typical 5.9 W
type of calculation of power loss depending on pole quadratic
insulation voltage
● of main circuit with degree of pollution 3 rated value 690 V
● of auxiliary circuit with degree of pollution 3 rated value 690 V
surge voltage resistance
● of main circuit rated value 6 kV
● of auxiliary circuit rated value 6 kV
maximum permissible voltage for protective separation between
coil and main contacts according to EN 60947-1
400 V
shock resistance at rectangular impulse
● at DC 10g / 5 ms, 7,5g / 10 ms
shock resistance with sine pulse
● at DC 15g / 5 ms, 10g / 10 ms
mechanical service life (operating cycles)
● of contactor typical 10 000 000
● of the contactor with added electronically optimized
auxiliary switch block typical
5 000 000
● of the contactor with added auxiliary switch block typical 10 000 000
reference code according to IEC 81346-2 Q
Substance Prohibitance (Date) 10/01/2009
Ambient conditions
installation altitude at height above sea level maximum 2 000 m
ambient temperature
● during operation -25 ... +60 °C
● during storage -55 ... +80 °C
relative humidity minimum 10 %
relative humidity at 55 °C according to IEC 60068-2-30
maximum
95 %
Environmental footprin
Environmental Product Declaration(EPD) Yes
Global Warming Potential [CO2 eq] total 221 kg
Global Warming Potential [CO2 eq] during manufacturing 2.65 kg
Global Warming Potential [CO2 eq] during operation 219 kg
Global Warming Potential [CO2 eq] after end of life -0.639 kg
Main circuit
number of poles for main current circuit 3
number of NO contacts for main contacts 3
operating voltage
● at AC-3 rated value maximum 690 V
● at AC-3e rated value maximum 690 V
operational current
● at AC-1 at 400 V at ambient temperature 40 °C rated
value
40 A
● at AC-1
— up to 690 V at ambient temperature 40 °C rated
value
40 A
— up to 690 V at ambient temperature 60 °C rated
value
35 A
● at AC-3
— at 400 V rated value 25 A
— at 500 V rated value 18 A
— at 690 V rated value 13 A
● at AC-3e
— at 400 V rated value 25 A
— at 500 V rated value 18 A
— at 690 V rated value 13 A
● at AC-4 at 400 V rated value 15.5 A
● at AC-5a up to 690 V rated value 35.2 A
● at AC-5b up to 400 V rated value 20.7 A
● at AC-6a
— up to 230 V for current peak value n=20 rated value 20.2 A
— up to 400 V for current peak value n=20 rated value 20.2 A
— up to 500 V for current peak value n=20 rated value 20.2 A
— up to 690 V for current peak value n=20 rated value 12.9 A
● at AC-6a
— up to 230 V for current peak value n=30 rated value 13.5 A
— up to 400 V for current peak value n=30 rated value 13.5 A
— up to 500 V for current peak value n=30 rated value 13.5 A
— up to 690 V for current peak value n=30 rated value 13 A
minimum cross-section in main circuit at maximum AC-1 rated
value
10 mm²
operational current for approx. 200000 operating cycles at
AC-4
● at 400 V rated value 9 A
● at 690 V rated value 9 A
operational current
● at 1 current path at DC-1
— at 24 V rated value 35 A
— at 60 V rated value 20 A
— at 110 V rated value 4.5 A
— at 220 V rated value 1 A
— at 440 V rated value 0.4 A
— at 600 V rated value 0.25 A
● with 2 current paths in series at DC-1
— at 24 V rated value 35 A
— at 60 V rated value 35 A
— at 110 V rated value 35 A
— at 220 V rated value 5 A
— at 440 V rated value 1 A
— at 600 V rated value 0.8 A
● with 3 current paths in series at DC-1Environmental Product Declaration(EPD) Yes
Global Warming Potential [CO2 eq] total 221 kg
Global Warming Potential [CO2 eq] during manufacturing 2.65 kg
Global Warming Potential [CO2 eq] during operation 219 kg
Global Warming Potential [CO2 eq] after end of life -0.639 kg
Main circuit
number of poles for main current circuit 3
number of NO contacts for main contacts 3
operating voltage
● at AC-3 rated value maximum 690 V
● at AC-3e rated value maximum 690 V
operational current
● at AC-1 at 400 V at ambient temperature 40 °C rated
value
40 A
● at AC-1
— up to 690 V at ambient temperature 40 °C rated
value
40 A
— up to 690 V at ambient temperature 60 °C rated
value
35 A
● at AC-3
— at 400 V rated value 25 A
— at 500 V rated value 18 A
— at 690 V rated value 13 A
● at AC-3e
— at 400 V rated value 25 A
— at 500 V rated value 18 A
— at 690 V rated value 13 A
● at AC-4 at 400 V rated value 15.5 A
● at AC-5a up to 690 V rated value 35.2 A
● at AC-5b up to 400 V rated value 20.7 A
● at AC-6a
— up to 230 V for current peak value n=20 rated value 20.2 A
— up to 400 V for current peak value n=20 rated value 20.2 A
— up to 500 V for current peak value n=20 rated value 20.2 A
— up to 690 V for current peak value n=20 rated value 12.9 A
● at AC-6a
— up to 230 V for current peak value n=30 rated value 13.5 A
— up to 400 V for current peak value n=30 rated value 13.5 A
— up to 500 V for current peak value n=30 rated value 13.5 A
— up to 690 V for current peak value n=30 rated value 13 A
minimum cross-section in main circuit at maximum AC-1 rated
value
10 mm²
operational current for approx. 200000 operating cycles at
AC-4
● at 400 V rated value 9 A
● at 690 V rated value 9 A
operational current
● at 1 current path at DC-1
— at 24 V rated value 35 A
— at 60 V rated value 20 A
— at 110 V rated value 4.5 A
— at 220 V rated value 1 A
— at 440 V rated value 0.4 A
— at 600 V rated value 0.25 A
● with 2 current paths in series at DC-1
— at 24 V rated value 35 A
— at 60 V rated value 35 A
— at 110 V rated value 35 A
— at 220 V rated value 5 A
— at 440 V rated value 1 A
— at 600 V rated value 0.8 A
● with 3 current paths in series at DC-1
— at 24 V rated value 35 A
— at 60 V rated value 35 A
— at 110 V rated value 35 A
— at 220 V rated value 35 A
— at 440 V rated value 2.9 A
— at 600 V rated value 1.4 A
● at 1 current path at DC-3 at DC-5
— at 24 V rated value 20 A
— at 60 V rated value 5 A
— at 110 V rated value 2.5 A
— at 220 V rated value 1 A
— at 440 V rated value 0.09 A
— at 600 V rated value 0.06 A
● with 2 current paths in series at DC-3 at DC-5
— at 24 V rated value 35 A
— at 60 V rated value 35 A
— at 110 V rated value 15 A
— at 220 V rated value 3 A
— at 440 V rated value 0.27 A
— at 600 V rated value 0.16 A
● with 3 current paths in series at DC-3 at DC-5
— at 24 V rated value 35 A
— at 60 V rated value 35 A
— at 110 V rated value 35 A
— at 220 V rated value 10 A
— at 440 V rated value 0.6 A
— at 600 V rated value 0.6 A
operating power
● at AC-3
— at 230 V rated value 5.5 kW
— at 400 V rated value 11 kW
— at 500 V rated value 11 kW
— at 690 V rated value 11 kW
● at AC-3e
— at 230 V rated value 5.5 kW
— at 400 V rated value 11 kW
— at 500 V rated value 11 kW
— at 690 V rated value 11 kW
operating power for approx. 200000 operating cycles at AC4
● at 400 V rated value 4.4 kW
● at 690 V rated value 7.7 kW
operating apparent power at AC-6a
● up to 230 V for current peak value n=20 rated value 8 kVA
● up to 400 V for current peak value n=20 rated value 13.9 kVA
● up to 500 V for current peak value n=20 rated value 17.4 kVA
● up to 690 V for current peak value n=20 rated value 15.4 kVA
operating apparent power at AC-6a
● up to 230 V for current peak value n=30 rated value 5.3 kVA
● up to 400 V for current peak value n=30 rated value 9.3 kVA
● up to 500 V for current peak value n=30 rated value 11.6 kVA
● up to 690 V for current peak value n=30 rated value 15.5 kVA
short-time withstand current in cold operating state up to
40 °C
● limited to 1 s switching at zero current maximum 375 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 5 s switching at zero current maximum 300 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 10 s switching at zero current maximum 210 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 30 s switching at zero current maximum 144 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 60 s switching at zero current maximum 118 A; Use minimum cross-section acc. to AC-1 rated value
no-load switching frequency
● at DC 1 500 1/h
operating frequency
● at AC-1 maximum 1 000 1/h
● at AC-2 maximum 750 1/h
● at AC-3 maximum 750 1/h
● at AC-3e maximum 750 1/h
● at AC-4 maximum 250 1/h
Control circuit/ Control
type of voltage of the control supply voltage DC
control supply voltage at DC rated value
● 220 V
operating range factor control supply voltage rated value of
magnet coil at DC
● initial value 0.8
● full-scale value 1.1
closing power of magnet coil at DC 5.9 W
holding power of magnet coil at DC 5.9 W
closing delay
● at DC 50 ... 170 ms
opening delay
● at DC 15 ... 18 ms
arcing time 10 ... 10 ms
control version of the switch operating mechanism Standard A1 - A2
Auxiliary circuit
number of NC contacts for auxiliary contacts instantaneous
contact
1
number of NO contacts for auxiliary contacts instantaneous
contact
1
operational current at AC-12 maximum 10 A
operational current at AC-15
● at 230 V rated value 10 A
● at 400 V rated value 3 A
● at 500 V rated value 2 A
● at 690 V rated value 1 A
operational current at DC-12
● at 24 V rated value 10 A
● at 48 V rated value 6 A
● at 60 V rated value 6 A
● at 110 V rated value 3 A
● at 125 V rated value 2 A
● at 220 V rated value 1 A
● at 600 V rated value 0.15 A
operational current at DC-13
● at 24 V rated value 10 A
● at 48 V rated value 2 A
● at 60 V rated value 2 A
● at 110 V rated value 1 A
● at 125 V rated value 0.9 A
● at 220 V rated value 0.3 A
● at 600 V rated value 0.1 A
contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)