Product data sheet
Rated Operational Voltage:
acc. to IEC 60898-1 400 V
Operational Voltage:
Maximum (Incl. Tolerance) 440 V AC
Minimum 12 V AC
Rated Insulation Voltage (Ui):
acc. to IEC/EN 60664-1 440 V
Rated Impulse Withstand Voltage (Uimp):
4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
Dielectric Test Voltage:
50/60 Hz, 1 min: 2 kV
Input Voltage Type:
AC
Rated Current (In):
50 A
Rated Short-Circuit Capacity:
(AC) 6 kA
(400 V AC) 6 kA
Rated Conditional Short-Circuit Current (Inc):
(230 V) 6 kA
(400 V) 6 kA
Rated Frequency (f):
50 / 60 Hz
Power Loss:
9.75 W
at Rated Operating Conditions per Pole 3.25 W
Power Supply Connection:
Arbitrary
Contact Position Indication:
ON / OFF
Energy Limiting Class:
3
Electrical Endurance:
10000 AC cycle
Mechanical Endurance:
20000 cycle
Number of Protected Poles:
3
Number of Poles:
3
Overvoltage Category:
III
Tightening Torque:
2 N·m