Menu
Your Cart

Control Monitor with flow sensor VS2000 ExiSR 2301

Control Monitor with flow sensor VS2000 ExiSR 2301
Control Monitor with flow sensor VS2000 ExiSR 2301
  • MODEL: VS2000 ExiSR 2301
  • LEAD TIME: 8-12weeks
$772.27

Product data sheet

Application
ApplicationFlow monitoring; Wire break monitoring
Electrical data
Operating voltage tolerance [%]-10...10
Operating voltage [V]24 DC
Current consumption [mA]125
Reverse polarity protectionno
Power-on delay time [s]30
Number of channels1
Outputs
Electrical designRelay
Contact rating4 A (250 V AC cos phi > 0,7) ; 0,2 A (250 V DC); 4 A (24 V DC)
Switching function flow monitoringrelay energized when flow is present
Switching function wire break monitoringrelay de-energized in case of wire break
Short-circuit proofno
Overload protectionno
Software / programming
Adjustment of the switch pointpotentiometer
Selection liquids / gaseswith slide switch
Operating conditions
Ambient temperature [°C]-20...60
ProtectionIP 40
Protection rating terminalsIP 20
Tests / approvals
ApprovalPTB 01 ATEX 2075; IECEx PTB 07.0004
ATEX marking II (1) G [Ex ia Ga] IIC
MTTF [years]231
Mechanical data
Weight [g]352.5
Housinghousing for DIN rail mounting
Dimensions [mm]78 x 45 x 120
Materialplastics
Displays / operating elements
Display
Function11 x LED
Switching statusLED, red
Electrical connection
Required protectionminiature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting; Place the fuse outside the hazardous area.
Remarks
Remarks
Caution The control monitor must be mounted outside the hazardous area.
Recommendation Check the safe functioning of the unit after a short circuit.
Pack quantity1 pcs.
Electrical connection
Connectionterminals: 15 x ...2.5 mm²
Other data
Maximum values for control circuit
in protection rating intrinsic safety[EEx ia] IIC[EEx ia] IIB[EEx ib] IIC[EEx ib] IIB
Voltage [V]15.815.815.815.8
Current [mA]84848484
Power [mW]680680680680
External inductance [mH]1111
External capacitance [µF]0.2051.70.205