Product data sheet
Synchronisation time between
inputs
0.5 s
2 s
4 s
Type of start Automatic/manual/monitored
Power consumption in W 3 W 24 V DC
Power consumption in VA 6.5 VA 24 V AC 50/60 Hz
Input protection type Internal, electronic
safety outputs 1 NC configurable
3 NO configurable
3 NO immediate
safety inputs 2 positive safety input 24 V DC 8 mA
1 negative safety input
maximum wire resistance 500 Ohm
Time delay range 0...900 s off
control outputs 4 on/off configurable pulsed output
Input/output type Semiconductor output 24 V DC, 20 mA Z2, not safety-related
Pulsed output for diagnostics 24 V DC, 20 mA Z1, not safety-related
[Ith] conventional free air thermal
current
16 A
Associated fuse rating 10 A gG NO relay output circuit IEC 60947-1
Minimum output current 20 mA relay output
Minimum output voltage 24 V relay output
Maximum response time on input
open
20 ms
[Ui] rated insulation voltage 250 V 2)IEC 60947-1
[Uimp] rated impulse withstand
voltage
4 kV II IEC 60947-1
Mounting Support 35 mm symmetrical DIN rail
Depth 4.7 in (120 mm)
Height 3.9 in (100 mm)
Width 1.8 in (45 mm)
Net Weight 0.772 lb(US) (0.350 kg)