 Contactor, LC1D32M7C
Contactor, LC1D32M7C
  • MODEL: LC1D32M7C
  • LEAD TIME: 3-5 days
$16.00

Product data sheet

Device short nameLC1D
contactor applicationResistive load
Motor control
Utilisation categoryAC-4
AC-1
AC-3
AC-3e
poles description3P
[Ue] rated operational voltagePower circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current32 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
50 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
32 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage220 V AC 50/60 Hz

Complementary
Motor power kW7.5 kW at 220...230 V AC 50/60 Hz (AC-3)
15 kW at 380...400 V AC 50/60 Hz (AC-3)
15 kW at 415...440 V AC 50/60 Hz (AC-3)
18.5 kW at 500 V AC 50/60 Hz (AC-3)
18.5 kW at 660...690 V AC 50/60 Hz (AC-3)
7.5 kW at 400 V AC 50/60 Hz (AC-4)
7.5 kW at 220...230 V AC 50/60 Hz (AC-3e)
15 kW at 380...400 V AC 50/60 Hz (AC-3e)
15 kW at 415...440 V AC 50/60 Hz (AC-3e)
18.5 kW at 500 V AC 50/60 Hz (AC-3e)
18.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating2 hp at 115 V AC 50/60 Hz for 1 phase motors
5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
10 hp at 200/208 V AC 50/60 Hz for 3 phase motors
10 hp at 230/240 V AC 50/60 Hz for 3 phase motors
20 hp at 460/480 V AC 50/60 Hz for 3 phase motors
25 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Compatibility codeLC1D
Pole contact composition3 NO
Protective coverWith
[Ith] conventional free air thermal current10 A (at 140 °F (60 °C)) for signalling circuit
50 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
550 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity550 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current260 A 104 °F (40 °C) - 10 s for power circuit
430 A 104 °F (40 °C) - 1 s for power circuit
60 A 104 °F (40 °C) - 10 min for power circuit
138 A 104 °F (40 °C) - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V coordination type 1 for power circuit
63 A gG at <= 690 V coordination type 2 for power circuit
Average impedance2 mOhm - Ith 50 A 50 Hz for power circuit
Power dissipation per pole2 W AC-3
5 W AC-1
2 W AC-3e
[Ui] rated insulation voltagePower circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage6 kV IEC 60947
Safety reliability levelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability15 Mcycles
Electrical durability1.65 Mcycles 32 A AC-3 <= 440 V
1.4 Mcycles 50 A AC-1 <= 440 V
1.65 Mcycles 32 A AC-3e <= 440 V
Control circuit typeAC 50/60 Hz standard
Coil technologyWithout built-in suppressor module
Control circuit voltage limits0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz
0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz
0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz
1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
Inrush power in VA70 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
70 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA7.5 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
7 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation2…3 W at 50/60 Hz
Operating time12...22 ms closing
4...19 ms opening
Maximum operating rate3600 cyc/h 140 °F (60 °C)