-800x800h.png)
Product data sheet
Rated Control Circuit Voltage (Uc)
50 Hz 220-230V; 60 Hz 230-240V
Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1
8 x Ie AC-3
Rated Operational Power AC-3 (Pe)
(220 / 230 / 240 V) 2.2 KWT, (380 / 400 V) 4 KWT, (415 V) 4 KWT, (440 V) 4 KWT, (500 V) 5.5 KWT, (690 V) 5.5 KWT
Rated Operational Current DC-13 (Ie)
(125 V) 1.1 / 138 ampere, (24 V) 6 / 144 ampere, (250 V) 0.55 / 138 ampere, (48 V) 2.8 / 134 ampere, (72 V) 2 / 144 ampere
Rated Operational Current AC-3 (Ie)
(220 / 230 / 240 V) 55 °C 9 ampere, (380 / 400 V) 55 °C 9 ampere, (415 V) 55 °C 9 ampere, (440 V) 55 °C 9 ampere, (500 V) 55 °C 9 ampere, (690 V) 55 °C 7 ampere
Rated Operational Current AC-15 (Ie)
(220 / 240 V) 4 ampere, (24 / 127 V) 6 ampere, (380 / 440 V) 3 ampere, (500 V) 2 ampere, (690 V) 2 ampere
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 25 ampere, (690 V) 55 °C 22 ampere, (690 V) 70 °C 18 ampere
Rated Making Capacity AC-3 acc. to IEC 60947-4-1
10 x Ie AC-3
Rated Breaking Capacity acc. to IEC 60947-5-1
10 x Ie AC-15
Rated Frequency Limits
25 ... 400 hertz
Rated Frequency (f)
Supply Circuit 50 60 hertz
Number of Aux Contacts NO
1
Package Width
78 millimetre
Package Length
76 millimetre
Package Height
47 millimetre
Package Gross Weight
0.34 kilogram