Product data sheet
Circular Value
Circular Design Principles Recyclability Rate:
Design for Closing Resource Loops - Standard EN45555 - 55.9 %
End of Life Instructions:
Group Waste to Landfill Target:
UL 2799 Zero Waste To Landfill Validation available
Eco Transparency
Environmental Product Declaration - EPD:
Environmental
Environmental Information:
Material Compliance
REACH Declaration:
RoHS Information:
RoHS Status:
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT):
Toxic Substances Control Act - TSCA:
SCIP:
0ac951c1-9b40-4f47-a751-2ab056ffe1d8 Italy (IT)
Simplified SCIP:
47481f31-3db7-43fa-90e7-510370035ce9 Germany (DE)
3d1957e6-6fff-4ac5-a4de-caa94ab5c364 France (FR)
585d169a-087c-4da7-ad22-14f7211e98a1 Netherlands (NL)
ff4fab3b-79ba-48cf-8ed4-5efe459324fa Estonia (EE)
f70a208d-8500-4b87-8e80-56eb4dcb62f2 Greece (GR)
ab874939-835a-44db-8d0f-0ae656d2b42c Portugal (PT)
3d1957e6-6fff-4ac5-a4de-caa94ab5c364 France (FR)
bd36d84d-14a0-4614-8240-3ca69ef29c39 Sweden (SE)
9be1dbef-ca32-4fe8-b574-89b5a88b48ee Germany (DE)
de6316e9-bdb1-43e5-b16d-b95b72c5dfb4 Germany (DE)
Ordering
Order Code US and Canada:
XT1NE4160AFF000XXX
E-Number (Sweden):
3182447
EAN:
8015644013226
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85362090
Dimensions
Product Net Width:
101.6 mm
Product Net Height:
130 mm
Product Net Depth / Length:
70 mm
Product Net Weight:
1.4 kg
Container Information
Package Level 1 Units:
box 1 piece
Package Level 1 Width:
128 mm
Package Level 1 Height:
135 mm
Package Level 1 Depth / Length:
143 mm
Package Level 1 Gross Weight:
1.47 kg
Package Level 1 EAN:
8015644013226
Additional Information
Circuit Breaker Type to be Associated:
Power Distribution
Product Main Type:
SACE Tmax XT
Product Name:
Moulded Case Circuit Breaker
Product Type:
Automatic Circuit Breaker
Version:
F
CAD Dimensional Drawing:
Technical
Connecting Capacity Main Circuit:
Busbar 45.5 ... 80 mm²
Current Type:
AC/DC
Electrical Durability:
120 cycles per hour
8000 cycle
Mechanical Durability:
240 cycles per hour
25000 cycle
Number of Poles:
4
Opening Time:
CB with SOR 15 ms
CB with UVR 15 ms
Order Multiple:
1 piece
Power Loss:
at Rated Operating Conditions per Pole 15 W
Rated Current (In):
160 A
Rated Frequency (f):
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp):
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii):
1600 A
Rated Insulation Voltage (Ui):
800 V
Rated Operational Voltage:
690 V AC
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics):
(220 V AC) 50 kA
(230 V AC) 50 kA
(240 V AC) 50 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 18 kA
(500 V AC) 15 kA
(525 V AC) 11 kA
(690 V AC) 5 kA
(250 V DC) 2 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(220 V AC) 65 kA
(230 V AC) 65 kA
(240 V AC) 65 kA
(380 V AC) 36 kA
(415 V AC) 36 kA
(440 V AC) 36 kA
(500 V AC) 30 kA
(525 V AC) 22 kA
(690 V AC) 6 kA
(250 V DC) 2 Poles in Series 36 kA
Rated Uninterrupted Current (Iu):
160 A
Rated Voltage (Ur):
690 V
Recommended Screw Driver:
Main Circuit M6
Release:
TMD
Release Type:
TM
Setting Range:
112...160 A
Short-Circuit Performance Level:
N
Standards:
IEC60947-2
Sub-type:
XT1
Terminal Connection Type:
Front
Terminal Type:
Bolt
Tightening Torque:
6 N·m
Certificates and Declarations
ATEX Certificate:
Data Sheet, Technical Information:
Declaration of Conformity - CE:
GL Certificate:
LR Certificate:
UL Certificate:
VDE Certificate:
Dimension Diagram:
Mechanical Drawings:
Wiring Diagram:
Instructions and Manuals:
Classifications
ETIM 8:
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9:
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code:
Q
UNSPSC:
39120000
WEEE Category:
5. Small Equipment (No External Dimension More Than 50 cm)
eClass:
V11.1 : 27370409
Tags:
ZORX-YMX20240821-04