Menu
Your Cart

Circuit Breaker,S201-C16, 2CDS251001R0164

Circuit Breaker,S201-C16, 2CDS251001R0164
Circuit Breaker,S201-C16, 2CDS251001R0164
  • MODEL: S201-C16
  • LEAD TIME: 8-12 weeks
$25.00

Product data sheet

Standards:
IEC/EN 60898-1
IEC/EN 60947-2
UL 1077
Tripping Characteristic:
C
Rated Operational Voltage:
acc. to IEC 60898-1 230 / 400 V AC
acc. to IEC 60898-1 230 V
acc. to IEC 60947-2 230 V AC
Operational Voltage:
Maximum (Incl. Tolerance) 253 V AC
Maximum (Incl. Tolerance) 72 V DC
Minimum 12 V AC
Minimum 12 V DC
Rated Insulation Voltage (Ui):
acc. to IEC/EN 60664-1 440 V
Rated Impulse Withstand Voltage (Uimp):
4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
Dielectric Test Voltage:
50/60 Hz, 1 min: 2 kV
Input Voltage Type:
AC/DC
Rated Current (In):
16 A
Rated Short-Circuit Capacity:
(AC) 6 kA
(DC) 6 kA
(230 / 400 V AC) 6 kA
(230 V) 6 kA
(400 V) 6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(133 V AC) 20 kA
(230 V AC) 10 kA
(24 V DC) 20 kA
(60 V DC) 10 kA
(230 V) 10 kA
(400 V) 10 kA
Rated Conditional Short-Circuit Current (Inc):
(230 V) 10 kA
(400 V) 10 kA
Rated Service Short-Circuit Breaking Capacity (Ics):
(133 V AC) 15 kA
(230 V AC) 7.5 kA
Frequency (f):
50 Hz
Rated Frequency (f):
50 / 60 Hz
Power Loss:
2.5 W
at Rated Operating Conditions per Pole 2.5 W
Power Supply Connection:
Arbitrary
Contact Position Indication:
Red ON / Green OFF
Energy Limiting Class:
3
Electrical Endurance:
20000 AC cycle
Mechanical Endurance:
20000 cycle
Number of Protected Poles:
1
Number of Poles:
1
Overvoltage Category:
III