Product data sheet
Number of Poles 3P
Application Power Distribution Protection
Number of poles 3
Nominal current [In] 16 A at 30 °C on ...
Grid type AC
Type of release Thermo-magnetic
Tripping curve C
Breaking capacity 6 kA Icn at ... 400 V AC 50/60 Hz per pole in accordance with GB/T 10963.1
6 kA Icn on ... 400 V AC 50/60 Hz per pole Conforms to IEC 60898-1
Category of use Class AC
Isolation function Applicable
Grid frequency 50/60 Hz
Rated operating voltage [Ue] 400 V AC 50/60 Hz
Magnetic stripping limit 5.... .10 x In
Current limitation class 3
Rated insulation voltage [Ui] 500 V AC
Rated impulse withstand voltage [Uimp] 6 kV
Contact position indication yes
Type of control Handle
Local signal indication Open/closed indication
Mounting type Locking clip locking
Mounting type DIN rail mounting
Width (multiples of 9 mm) 6
Height 94 mm
Depth 78.5 mm
Net weight 316 g
Mechanical life 20000 cycles
Electrical life 10000 cycles
Wiring capacity Tunnel terminal Upper or lower wire 1...25 mm² single hardwire without terminals
Tunnel terminal Upper or lower wire 1...16 mm² flexible wire (optional) with or without wire terminals
Stripping length Power supply circuit: 14 mm
Tightening torque Power supply circuit: 2.5 N.m.
Leakage current protection (required)