Product data sheet
Rated operating voltage [Ue] 230/400 V AC 50 Hz
Grid type AC
Grid frequency 50 Hz
Number of protection poles 2
Type of release Thermo-magnetic
Magnetic release limit 5.... .10 x In
Breaking capacity 6 kA Icn on 230/400 V AC 50 Hz
Using breaking capacity [Ics] 6 kA 100 % - 230/400 V AC 50 Hz
Current limiting class 3
Rated impulse withstand voltage [Uimp] 6 kV
Isolation function Applicable
Control type Handle
Contact position indication Yes
Local signal indication Open/closed indication
Overvoltage category IV
Mechanical life 20000 cycles
Electrical life 10000 cycles
Mounting type Locking clip locking
Mounting type DIN rail mounting
Color Handle: Orange (RAL 2003)
Lamp body: silver (Pantone 7541C)
Locking clip: light gray (RAL 7035)
Wiring capacity Tunnel terminal block - <= 25 mm²
Tightening torque 2.5 N.m Upper or lower connection
Width (multiples of 9 mm) 4
Height 81 mm
Width 35.4 mm - 0.2.... .0.5 mm
Depth 70 mm
Net weight 220 g