Product data sheet
Number of poles 3P
Description of protection poles 3D
Nominal current [In] 250 A at 40 °C on
Rated operating voltage [Ue] 690 V AC 50/60 Hz
Grid type AC
Grid frequency 50/60 Hz
Isolation function Applicable Conforms to TM-D
Class of use AC
[Icu] Rated ultimate short-circuit breaking capacity 85 kA Icu on 220/240 V AC 50/60 Hz in accordance with IEC 60947-2
36 kA Icu on ... 380/415 V AC 50/60 Hz according to IEC 60947-2
35 kA Icu on ... 440 V AC 50/60 Hz in accordance with IEC 60947-2
30 kA Icu on ... 500 V AC 50/60 Hz in accordance with IEC 60947-2
22 kA Icu on ... 525 V AC 50/60 Hz in accordance with IEC 60947-2
8 kA Icu on ... 660/690 V AC 50/60 Hz in accordance with IEC 60947-2
35 kA on... 480 V AC 50/60 Hz in accordance with UL 508
15 kA at ... 600 V AC 50/60 Hz in accordance with UL 508
Breaking capacity F 36 kA 415 V AC
Name of release TM-D
Type of release Thermo-magnetic
Tripper protection function LI
Control type Handle
Circuit Breaker Mounting Type Fixed