Product data sheet
Product Type Circuit Breaker
Application Power Distribution Protection
Number of Poles 3P
Description of protection poles 3D
Rated current [In] 160 A at ... up 40 °C
Rated operating voltage [Ue] 690 V AC 50/60 Hz
Grid type AC
Grid frequency 50/60 Hz
Isolation function Applicable Conforms to TM-D
Class of use AC
[Icu] Rated ultimate short-circuit breaking capacity 90 kA Icu on 220/240 V AC 50/60 Hz in accordance with IEC 60947-2
50 kA Icu on ... 380/415 V AC 50/60 Hz in accordance with IEC 60947-2
50 kA Icu on ... 440 V AC 50/60 Hz in accordance with IEC 60947-2
36 kA Icu on ... 500 V AC 50/60 Hz in accordance with IEC 60947-2
35 kA Icu on ... 525 V AC 50/60 Hz in accordance with IEC 60947-2
10 kA Icu on ... 660/690 V AC 50/60 Hz in accordance with IEC 60947-2
Breaking capacity N 50 kA 415 V AC
Name of disconnector TM-D
Type of release Thermo-magnetic
Function LI
Type of control Handle
Circuit breaker mounting type Fixed
Additional Information
Rated insulation voltage [Ui] 800 V AC 50/60 Hz
Rated impulse withstand voltage [Uimp] 8 kV
Rated operational short-circuit breaking capacity [Ics] 90 kA at ... 220/240 V AC 50/60 Hz in accordance with IEC 60947-2
50 kA at ... 380/415 V AC 50/60 Hz in accordance with IEC 60947-2
50 kA on ... 440 V AC 50/60 Hz in accordance with IEC 60947-2
36 kA at ... 500 V AC 50/60 Hz in accordance with IEC 60947-2
35 kA at ... 525 V AC 50/60 Hz in accordance with IEC 60947-2
10 kA on ... 660/690 V AC 50/60 Hz in accordance with IEC 60947-2
Mechanical life 40000
Electrical life 40000 cycles on 440 V In/2
20000 cycles 440 V In on ....
15000 cycles 690 V In/2 on ....
7500 cycles 690 V In on ...
Power consumption 13.95 W per pole
Mounting method Base plate mounting
Mounting position Horizontal and vertical
Flat on the back
Connection type - top Front connection
Connection type - bottom Front connection
Pole spacing 35 mm
Protection type L : for overload protection (thermal protection)
I : for short-circuit protection (magnetic protection)
Tripper rating 160 A at ... up 40 °C
Long delay current setting Ir (thermal protection) adjustable
[Ir] Long delay overcurrent threshold setting range 0.7...1 x In. ...1 x In
Long delay time setting type tr fixed
[tr] Long delay time protection delay setting range 120...400 s on ... 1.5 x In
15 s on ... 6 x Ir
Type of instantaneous overcurrent protection calibration Ii fixed
[Ii] Instantaneous overcurrent protection Threshold setting range 1250 A
Leakage current protection No leakage protection
Number of mounting slots for electrical accessories 5 slots
Width (W) 105 mm
Height (H) 161 mm
Depth (D) 86 mm
Net weight 2.2 kg
ENVIRONMENTAL
Standard EN/IEC 60947
Product Certification CCC
EAC
Marine
Overvoltage Category Class II
Electric shock protection class Class II
Pollution Class 3 conforming to IEC 60664-1
IP Protection Class IP40 conforming to IEC 60529
IK protection class IK07 conforming to IEC 62262
Operating temperature -25...70 °C
Storage ambient temperature -50...85 °C
Relative humidity 0...95 %
Operating altitude 0... .2000 m .2000 m without degradation
2000 m... .5000 m with reduced capacity