Product data sheet
Dimension
Product net width.
76.2 mm
Net height:
130 mm
Net Depth:
60 mm
Net weight:
0.79 kg
Electrical life:
1500 cycles
Mechanical life:
Nr. Operations 8500 cycles
Number of poles:
3
Total disconnection time
CB with SOR 15 ms
CB with UVR 15 ms
Power Loss: 6 W at Rated Operating Conditions per Pole
at Rated Operating Conditions per Pole 6 W
Rated Current (In): Main Circuit 63 A
Main Circuit 63 A
Rated Impulse Withstand Voltage (Uimp):
6 kV
Rated insulation voltage (Ui):
690 V
Rated operating voltage:
550 V AC
250 V DC
Rated service short-circuit breaking capacity (Ics).
(240 V AC) 15 kA
(380 V AC) 12.5 kA
(415 V AC) 6.25 kA
(440 V AC) 5 kA
(480 V AC) 4 kA
(500 V AC) 2.5 kA
(250 V DC) 2 Poles in Series 5 kA
Rated ultimate short-circuit breaking capacity (Icu).
(240 V AC) 30 kA
(380 V AC) 25 kA
(415 V AC) 25 kA
(440 V AC) 20 kA
(480 V AC) 15 kA
(500 V AC) 8 kA
(250 V DC) 10 kA
Rated continuous current (Iu).
125 A
Tripper:
TMF
Tripper type:
TMF
Short Circuit Performance Rating:
C
Standard:
IEC
Shell frame class:
A1
Terminal Connection Type:
Front