Product data sheet
[Ui] rated insulation voltage | 800 V AC 50/60 Hz |
---|---|
[Uimp] rated impulse withstand voltage | 8 kV |
[Ics] rated service short-circuit breaking capacity | 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical durability | 40000 cycles |
Electrical durability | 40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In |
Power dissipation per pole | 13.95 W |
mounting support | Backplate |
Mounting position | Horizontal and vertical Flat on the back |
Upside connection | Front |
downside connection | Front |
Connection pitch | 35 mm |
Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
Trip unit rating | 160 A at 40 °C |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
[Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
Long-time protection delay adjustment type tr | Fixed |
[tr] long-time protection delay adjustment range | 120…400 s at 1.5 x In 15 s at 6 x Ir |
Instantaneous protection pick-up adjustment type Ii | Fixed |
[Ii] instantaneous protection pick-up adjustment range | 1250 A |
Earth-leakage protection | Without |
Number of slots for electrical auxiliaries | 5 slot(s) |
Width (W) | 105 mm |
Height (H) | 161 mm |
Depth (D) | 86 mm |
net weight | 2.2 kg |
Tags:
HDL-QL24070507